Baldor FPM2568T-4, Fire Pump Motor, 250/300 HP, 380/460 Volts, 339 Amps, 3 Phase, 50/60 Hz, 3560/2960 RPM, OPEN Enclosure, 445TS Frame, Standard, A44072M Motor Type, Iron Frame

SKU #: FPM2568T-4
Brand: Baldor
Available For Order! (Ships in 1-2 Days)This product  is direct shipped from the manufacturer. The estimated shipping time may vary depending on the manufacturers stock, backlog or delay. If you would like to confirm the manufacturers lead time for this item, call our Pump Products sales team at 800-429-0800 between the hours of 7:30 A.M. - 4:30 P.M. E.S.T.
Order Item Now!
Call Sales Counter !
Order By Phone
Calculate Shipping Ship Weight (1,697.00 lbs)

FEATURES

Fire Pump motor is for use on fire pumps installed per NFPA-20. All motors meet UL requirements in open enclosures designed for relatively clean and dry environments.

Features

  • UL File E481231
  • 50/60 Hertz
  • 200/400V, 230/460V, 460V
  • Rolled Steel and Cast Iron Frames
  • Exterior Red Paint RAL3002
  • Class F Insulation system
  • 1.15 Service Factor, 40° C ambient continuous

Applications

  • Fire Suppression
  • Fire Pumps installed per NFPA-20

Note: Picture is illustrative and may not reflect the actual product

BrandBaldor
Mfg. NumberFPM2568T-4
Product TypeFire Pump Motor
Horsepower250/300 HP
Voltage380/460 Volts
Phase3
Frequency50/60 Hz
Synchronous Speed3600 RPM
Speed3560/2960 RPM
Speed CodeSingle Speed
High Voltage Full Load Amps, mps339 Amps
EnclosureOPEN
Frame Size445TS
Motor TypeA44072M
Motor StandardsNEMA
Number of Poles2
Pulley Face CodeStandard
Frame MaterialIron
Motor Lead Quantity/Wire Size12 @ 2 AWG
Overall Length35.88 in
Service Factor1.15
Efficiency @ 100% Load95.00%
Duty RatingCONT
Inverter CodeNot inverter
Mounting TypeFoot
Auxillary BoxNo
Base IndicatorRigid
Bearing Grease TypePOLYREX EM (-20F +300F)
Current342.0 A @ 380 V 339.0 A @ 460 V
Design CodeB
Drip CoverNo Drip Cover
Heater IndicatorNo heater
KVA CodeF
Motor Lead ExitKO Box
Motor Lead TerminationFlying Leads
Rodent ScreenNo
Shaft Diameter2.375 in
Insulation ClassF
Power Factor87
Pulley End Bearing TypeBall Bearing
Shaft Extension LocationPulley End
Shaft RotationReversible
Shaft Slinger IndicatorNo Slinger
Starting MethodWye Start - Delta Run
Vibration Sensor IndicatorNo Vibration Sensor
Thermal Device - BearingNo
Thermal Device - WindingNo
Ambient Temperature40 °C
Agency ApprovalsCCSA, US CSA, EEV, UL